Remarks |
UK importer address: Signify Commercial UK Limited, 3, Guildford Business Park, GU2 8XG
|
Application code |
E+
|
Type version |
mk2
|
Lamp type |
TL5
|
Number of lamps |
2 piece/unit
|
Number of products on MCB (16 A type B) (nom.) |
18
|
Automatic restart |
Yes
|
Input Voltage |
195-240 V
|
Input frequency |
50 to 60 Hz
|
Operating frequency (max.) |
110 kHz
|
Operating frequency (min.) |
45 kHz
|
Ignition method |
Warm Start
|
Crest factor (max.) |
1.7
|
Power factor 100% load (nom.) |
0.95
|
Ignition time (max.) |
1 s
|
Mains voltage performance (AC) |
-8%-+6%
|
Mains voltage safety (AC) |
-10%-+10%
|
Earth leakage current (max.) |
0.5 mA
|
Inrush current width |
0.25 ms
|
Standby power consumption (max.) |
0.25 W
|
Ballast factor (nom.) |
1
|
Power losses (nom.) |
7.2 W
|
Inrush current peak (max.) |
28 A
|
Connector type input terminals |
WAGO 251 universal connector [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
|
Cable capacity output wires mutual (max.) |
200 pF
|
Connector type output terminals |
WAGO 251 universal connector [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
|
Connector type control input terminals |
WAGO 251 universal connector [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
|
Wire strip length |
8.0-9.0 mm
|
Dual fixture master/slave |
Yes [ Master/Slave operation possible]
|
Control input terminal cross section |
0.50-1.00 mm²
|
Input terminal cross section |
0.50-1.00 mm²
|
Output terminal cross section |
0.50-1.00 mm²
|
Auto-insert (ALF/ADS) wire cross section |
0.75 mm²
|
Cable capacity output wires to earth (max.) |
200 pF
|
Rated ballast-lamp power |
28-35-49-54 W
|
Rated lamp power on TL-D |
58 W
|
System power on TL-D |
108.1 W
|
Lamp power on TL-D |
101.1 W
|
Power loss on TL-D |
7.1 W
|
Rated lamp power on PL-L |
55 W
|
System power on PL-L |
108.4 W
|
Lamp power on PL-L |
101.6 W
|
Power loss on PL-L |
6.8 W
|
Rated lamp power on TL5 |
28/35/49/54 W
|
System power on TL5 |
63.0/77.9/111.4 W
|
Lamp power on TL5 |
58.9/73.6/107.2/113.4 W
|
Power loss on TL5 |
4.1/4.3/4.2/6.3 W
|
Rated lamp power on TL5 ECO |
25/32/45/50 W
|
System power on TL5 ECO |
53.7/70.3/99.7/108.7 W
|
Lamp Power on TL5 ECO |
50.8/66.5/95.6/102.7 W
|
Rated lamp power on TL-D ECO |
51 W
|
System power on TL-D ECO |
95.8 W
|
Power loss on TL-D ECO |
6.0 W
|
Lamp power on TL-D ECO |
89.8 W
|
Power loss on TL5 ECO |
2.9/3.8/4.1/6.0 W
|
T-ambient (max.) |
50 °C
|
T-ambient (min.) |
-25 °C
|
T storage (max.) |
80 °C
|
T storage (min.) |
-40 °C
|
T case lifetime (max.) |
75 °C
|
T-Case maximum (max.) |
75 °C
|
Stable lamp operation temperature |
15°C
|
T-Ignition (max.) |
50 °C
|
T-Ignition (min.) |
-25 °C
|
Control interface |
TD
|
Regulating level power |
1%-100%
|
Control input protection |
Yes (Basic insulation)
|
Housing |
L 359x30x21
|
Battery voltage lamp ignition |
198-254 V
|
Battery voltage lamp operation |
176-254
|
Energy efficiency index |
A1 BAT
|
IP classification |
IP 20 [ Ingress Protection 20]
|
EMI 9 kHz ... 30 MHz |
EN55015
|
EMI 30 MHz ... 1,000 MHz |
EN 55022 Class B
|
Safety standard |
IEC 61347-2-3
|
Performance standard |
IEC 60929
|
Quality standard |
ISO 9000:2000
|
Environmental standard |
ISO 14001
|
Harmonic current emission standard |
IEC 61000-3-2
|
EMC immunity standard |
IEC 61547
|
Vibration standard |
IEC68-2-6 F c
|
Bumps standard |
IEC 68-2-29 Eb
|
Humidity standard |
EN 61347-2-3 clause 11
|
Approval marks |
CE marking ENEC certificate VDE-EMV certificate |
Temperature marking |
Yes
|
Emergency standard |
IEC 60598-2-22
|
Humming and noise level |
Inaudible
|
Full product code |
871829166209900
|
Order product name |
HF-Ri TD 2 28/35/49/54 TL5 E+ 195-240V
|
EAN/UPC – product |
8718291662099
|
Order code |
66209900
|
Local order code |
HFRITD22854T5PL
|
SAP numerator – quantity per pack |
1
|
Numerator – packs per outer box |
12
|
SAP material |
913700695866
|
SAP net weight (piece) |
0.316 kg
|